DocumentCode
2509376
Title
Preliminary evaluation of a qualitative model-based fault detector for a central air-handling unit
Author
Glass, A.S. ; Gruber, P. ; Roos, M. ; Tödtli, J.
Author_Institution
Landis & Gyr Betriebs AG, Zug, Switzerland
fYear
1994
fDate
24-26 Aug 1994
Firstpage
1873
Abstract
The feasibility of a qualitative approach for detecting faults in an air-conditioning system is considered. The system considered is a multi-zone variable air volume air-handling unit, and the faults investigated include types which result in deterioration of operation as distinct from actual failure. The operating modes of the sequential controller for the central air-handling plant can be matched to a corresponding qualitative classification of steady-state temperatures. Observed mismatches indicate the presence of faults. First trials of the method in an air-conditioning test laboratory are reported
Keywords
air conditioning; fault diagnosis; predictive control; temperature control; air-conditioning system; central air-handling unit; operation deterioration; qualitative classification; qualitative model-based fault detector; sequential controller; temperature control; Air conditioning; Fault diagnosis; Predictive control; Temperature control;
fLanguage
English
Publisher
ieee
Conference_Titel
Control Applications, 1994., Proceedings of the Third IEEE Conference on
Conference_Location
Glasgow
Print_ISBN
0-7803-1872-2
Type
conf
DOI
10.1109/CCA.1994.381249
Filename
381249
Link To Document