Lightning protection of a pharmaceutical plant, measurements and modelling
Author :
Bargboer, G. ; van Deursen, A.P.J.
Author_Institution :
Dept. of Electr. Eng., Eindhoven Univ. of Technol., Eindhoven, Netherlands
fYear :
2010
fDate :
12-16 April 2010
Firstpage :
1193
Lastpage :
1196
Abstract :
The lightning protection of a pharmaceutical plant has been tested by current-injection on the structure. The study aims at two goals: 1) proof of safety by scaling the currents and voltage to lightning realistic values and 2) a comparison between measurements and a Method of Moments calculation. We measured the current distribution near the source and the induced currents and voltages in test cables. The cables and their 100 m long path were representative for the actual installation. By necessity the model is simplified, because of the large number of conductors, intended and unintended, and the uncertainty of their interconnection. The calculated currents are a factor of 3 larger than measured.
Keywords :
lightning protection; method of moments; pharmaceutical technology; power generation protection; power plants; conductors; lightning protection; method of moments; pharmaceutical plant; size 100 m; Cables; Conductors; Current distribution; Current measurement; Lightning protection; Moment methods; Pharmaceuticals; Safety; Testing; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electromagnetic Compatibility (APEMC), 2010 Asia-Pacific Symposium on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-5621-5
Type :
conf
DOI :
10.1109/APEMC.2010.5475762
Filename :
5475762
Link To Document :
بازگشت