• DocumentCode
    2515755
  • Title

    Stability control of TCSC between interconnected power networks

  • Author

    Guo Chunlin ; Luyuan, Tong ; Zhonghong, Wang

  • Author_Institution
    Tsinghua Univ., Beijing, China
  • Volume
    3
  • fYear
    2002
  • fDate
    2002
  • Firstpage
    1943
  • Abstract
    TCSC is a FACTS device installed in a long transmission line to improve its power transmission ability. By simulations, this paper investigates the influence of the phase and amplitude of TCSC output on the power oscillation of a 2-area interconnected system. The result indicates, when the compensation degree of TCSC increases, its effect will reach a pink value just like a saturation phenomenon. When the compensation degree is suitable, the phase of TCSC output has a more significant impact on the oscillation than the amplitude. In order to improve the damping of the system, TCSC is found to be a better choice than traditional series compensation or two parallel lines.
  • Keywords
    compensation; control system analysis; damping; flexible AC transmission systems; power system interconnection; power system stability; power transmission control; power transmission lines; reactive power control; thyristor convertors; FACTS device; TCSC; compensation degree; interconnected power networks; long transmission line; power oscillation damping; saturation phenomenon; stability control; thyristor controlled series compensation; Automatic control; Control systems; Damping; Frequency; Load flow; Nonlinear control systems; Power capacitors; Power system stability; Power system transients; Thyristors;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power System Technology, 2002. Proceedings. PowerCon 2002. International Conference on
  • Print_ISBN
    0-7803-7459-2
  • Type

    conf

  • DOI
    10.1109/ICPST.2002.1067872
  • Filename
    1067872