DocumentCode :
2521944
Title :
Accelerated testing of outdoor power equipment
Author :
Krivda, A. ; Singh, B. ; Carlen, M. ; Hartmann, T. ; Schaal, S. ; Mahonen, P. ; Le, H. ; Tzavalas, S.
Author_Institution :
Corp. Res., ABB Switzerland Ltd., Baden-Daettwil, Switzerland
fYear :
2011
fDate :
16-19 Oct. 2011
Firstpage :
381
Lastpage :
386
Abstract :
In this work we summarize the results of long-term ageing of different medium voltage outdoor power equipment in an artificial climatic chamber and compare them with the results obtained at a natural ageing site at the Koeberg Insulator Pollution Test Station near Cape Town, South Africa. The results show that by correctly adjusting the ageing cycle consisting of UV radiation, heat, clean and salt fog it is possible to age power equipment at an accelerated rate (a factor of 5 and greater) and obtain the same type of damage (UV damage, tracking and erosion due to surface discharges, cracking) as observed at the natural ageing site. Although many different types of outdoor power equipment will still have to be tested, the first results based on epoxy insulated power equipment are encouraging.
Keywords :
ageing; epoxy insulation; power apparatus; UV radiation; accelerated testing; ageing cycle; artificial climatic chamber; epoxy insulated power equipment; fog; heat; natural ageing; outdoor power equipment; Aging; Coils; Degradation; Insulators; Materials; Surface discharges; Surface treatment;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena (CEIDP), 2011 Annual Report Conference on
Conference_Location :
Cancun
ISSN :
0084-9162
Print_ISBN :
978-1-4577-0985-2
Type :
conf
DOI :
10.1109/CEIDP.2011.6232675
Filename :
6232675
Link To Document :
بازگشت