Title :
Analysis of the performance of nonceramic insulators on 230 kV and 400 kV transmission lines
Author :
Hernández, Ramiro ; Ramirez, Isaías ; Montoya, Gerardo
Author_Institution :
Inst. de Investig. Electr. (IIE), Morelos, Mexico
Abstract :
Nonceramic insulators have been applied in Mexico for about 15 years under various polluted conditions on 230 kV and 400 kV transmission lines. The operative condition of nonceramic insulators from 3 to 11 years in service is analyzed. The analysis is carried out by measurements of hydrophobicity, pollution level, visual corona, Fourier transform infrared spectroscopy (FTIR) and thermal gravimetric (TGA). An ethylene propylene diene monomer rubber (EPDM) insulator of 31 mm/kV showed very light degradation on its surface after 9 years in service under non polluted conditions; although its hydrophobic property was low, signs of surface discharges were not observed. On polluted zones, silicone rubber (SiR) insulators are used. The most of the inspected insulators presented degradation on their housing. Severe damage was found on one insulator of 31 mm/kV which had been working for 2.4 years. The results show that the insulators with less damage and more time in service are those having a specific leakage distance of 39 mm/kV or a 52% of silicone rubber.
Keywords :
Fourier transform spectroscopy; corona; density measurement; ethylene-propylene rubber; hydrophobicity; infrared spectroscopy; insulator contamination; packaging; power cable insulation; power transmission lines; silicone rubber insulators; EPDM rubber insulator; FTIR; Fourier transform infrared spectroscopy; SiR insulators; TGA measurements; ethylene propylene diene monomer rubber insulator; housing; hydrophobicity measurements; insulator damage; leakage distance; nonceramic insulators; nonpolluted conditions; operative condition; performance analysis; polluted conditions; pollution level measurements; silicone rubber insulators; surface degradation; surface discharges; thermal gravimetric measurements; transmission lines; visual corona; voltage 230 kV; voltage 400 kV; Materials; Pollution; Power transmission lines; Rubber; Surface contamination; Transmission line measurements;
Conference_Titel :
Electrical Insulation and Dielectric Phenomena (CEIDP), 2011 Annual Report Conference on
Conference_Location :
Cancun
Print_ISBN :
978-1-4577-0985-2
DOI :
10.1109/CEIDP.2011.6232677