DocumentCode :
2522551
Title :
Lightning and switching impulse levels selection for long DC cable lines
Author :
Marzinotto, M. ; Mazzanti, G. ; Mazzetti, C.
Author_Institution :
TERNA, Roma, Italy
fYear :
2011
fDate :
16-19 Oct. 2011
Firstpage :
510
Lastpage :
513
Abstract :
The impulse test levels play an even more important role for the design of HVDC cables than for HVAC cables. Nevertheless, the selection of both lightning and switching impulse test values for a given power DC intertie are mostly based on numerical simulation and on past experience on similar interties rather than on well-established and standardized practices. In this paper the selection of lightning and switching impulse voltage levels to be applied on short cable lengths in the prequalification and/or type tests is addressed for long DC cable lines (longer than 50 km) taking into account the impulse withstand behaviour with cable length via the enlargement law and the effect of over-voltage attenuation for surges that travel along the cable.
Keywords :
impulse testing; lightning; numerical analysis; overvoltage; power cable testing; surges; HVAC cable; HVDC cable; cable surging; enlargement law; lightning selection; long DC cable line; numerical simulation; overvoltage attenuation effect; power DC intertie; short cable length; switching impulse test level selection; Cable insulation; Electric fields; Lightning; Power cables; Surges; Switches;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena (CEIDP), 2011 Annual Report Conference on
Conference_Location :
Cancun
ISSN :
0084-9162
Print_ISBN :
978-1-4577-0985-2
Type :
conf
DOI :
10.1109/CEIDP.2011.6232706
Filename :
6232706
Link To Document :
بازگشت