DocumentCode :
2522812
Title :
Parameters affecting the static electrification of aged transformer oils
Author :
N´Cho, J.S. ; Fofana, I. ; Beroual, A.
Author_Institution :
AMPERE, Ecole Centrale de Lyon, Ecully, France
fYear :
2011
fDate :
16-19 Oct. 2011
Firstpage :
571
Lastpage :
574
Abstract :
In this contribution, experimental investigations onto the factors affecting the static electrification of aged transformer oils are undertaken. The effect of aging byproducts (as assessed by Dissolved Decay products, Turbidity, Interfacial Tension and Acid number) of the oil on the streaming current is reported. The results indicate that the electrification currents generally increase with aging by-products of oil. The sign, the amplitude and the time constant of the electrification currents are also affected. The influence of each “impurity” is emphasized and discussed.
Keywords :
transformer oil; acid number; aged transformer oil static electrification; aging byproduct effect; dissolved decay products; electrification currents; interfacial tension; oil aging by-products; Aging; Current measurement; Insulation; Leakage current; Oils; Power transformer insulation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena (CEIDP), 2011 Annual Report Conference on
Conference_Location :
Cancun
ISSN :
0084-9162
Print_ISBN :
978-1-4577-0985-2
Type :
conf
DOI :
10.1109/CEIDP.2011.6232721
Filename :
6232721
Link To Document :