• DocumentCode
    2523540
  • Title

    Improving relay protection levels in medium voltage switchgear

  • Author

    Catlett, Raymond ; Martin, Daniel ; Wilson, Robert A.

  • Author_Institution
    ABB Inc., Collinsville, IL, USA
  • fYear
    2012
  • fDate
    24-26 Sept. 2012
  • Firstpage
    1
  • Lastpage
    10
  • Abstract
    This paper demonstrates the impacts of an electronically triggered fault current limiter (ET-FCL) on typical single-ended and main-tie-main (MTM) medium voltage (MV) switchgear arrangements. The fast acting (less than 1 ms) ET-FCL described in this paper effectively opens the normally-closed tie connection between two mains, thereby disconnecting one of the sources to the fault. An ultra-fast opening of the tie connection simplifies protection coordination by not having to coordinate the main breaker relay with the tie breaker relay at maximum fault levels. System benefits include: . Significantly lower arc flash energy for downstream faults; Faster backup clearing times for a feeder relay/breaker failure; Reduction of motor starter dropouts due to fault produced voltage dips; Improved system stability . Improvement in utility´s CAIDI reliability index; Reduced stress on switchgear breakers; Overall lower capital costs on new construction (switchgear, cables etc.). This paper demonstrates relay setting changes on typical single ended and MTM arrangement with and without applying the ET-FCL. Impacts on incident energy reduction, backup clearing times, dynamic system stability and voltage dips will be discussed.
  • Keywords
    circuit breakers; fault current limiters; relay protection; reliability; ET-FCL; MTM MV switchgear arrangements; arc flash energy; backup clearing times; capital costs; dynamic system stability; electronically triggered fault current limiter; fault levels; fault produced voltage dips; feeder relay-breaker failure; improved system stability; incident energy reduction; main-tie-main medium voltage switchgear arrangements; medium voltage switchgear breakers; motor starter dropout reduction; normally-closed tie connection; relay protection levels; single-ended MV switchgear arrangements; single-ended medium voltage switchgear arrangements; ultrafast opening; utility CAIDI reliability index; voltage dips; Circuit breaker interrupting time; fault current limiter (FCL); main-tie-main (MTM); power quality; protective device coordination; short circuit capacity (SCC);
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Petroleum and Chemical Industry Technical Conference (PCIC), 2012 Record of Conference Papers Industry Applications Society 59th Annual IEEE
  • Conference_Location
    Chicago, IL
  • ISSN
    0090-3507
  • Print_ISBN
    978-1-4673-0924-0
  • Type

    conf

  • DOI
    10.1109/PCICON.2012.6549649
  • Filename
    6549649