DocumentCode :
2523540
Title :
Improving relay protection levels in medium voltage switchgear
Author :
Catlett, Raymond ; Martin, Daniel ; Wilson, Robert A.
Author_Institution :
ABB Inc., Collinsville, IL, USA
fYear :
2012
fDate :
24-26 Sept. 2012
Firstpage :
1
Lastpage :
10
Abstract :
This paper demonstrates the impacts of an electronically triggered fault current limiter (ET-FCL) on typical single-ended and main-tie-main (MTM) medium voltage (MV) switchgear arrangements. The fast acting (less than 1 ms) ET-FCL described in this paper effectively opens the normally-closed tie connection between two mains, thereby disconnecting one of the sources to the fault. An ultra-fast opening of the tie connection simplifies protection coordination by not having to coordinate the main breaker relay with the tie breaker relay at maximum fault levels. System benefits include: . Significantly lower arc flash energy for downstream faults; Faster backup clearing times for a feeder relay/breaker failure; Reduction of motor starter dropouts due to fault produced voltage dips; Improved system stability . Improvement in utility´s CAIDI reliability index; Reduced stress on switchgear breakers; Overall lower capital costs on new construction (switchgear, cables etc.). This paper demonstrates relay setting changes on typical single ended and MTM arrangement with and without applying the ET-FCL. Impacts on incident energy reduction, backup clearing times, dynamic system stability and voltage dips will be discussed.
Keywords :
circuit breakers; fault current limiters; relay protection; reliability; ET-FCL; MTM MV switchgear arrangements; arc flash energy; backup clearing times; capital costs; dynamic system stability; electronically triggered fault current limiter; fault levels; fault produced voltage dips; feeder relay-breaker failure; improved system stability; incident energy reduction; main-tie-main medium voltage switchgear arrangements; medium voltage switchgear breakers; motor starter dropout reduction; normally-closed tie connection; relay protection levels; single-ended MV switchgear arrangements; single-ended medium voltage switchgear arrangements; ultrafast opening; utility CAIDI reliability index; voltage dips; Circuit breaker interrupting time; fault current limiter (FCL); main-tie-main (MTM); power quality; protective device coordination; short circuit capacity (SCC);
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Petroleum and Chemical Industry Technical Conference (PCIC), 2012 Record of Conference Papers Industry Applications Society 59th Annual IEEE
Conference_Location :
Chicago, IL
ISSN :
0090-3507
Print_ISBN :
978-1-4673-0924-0
Type :
conf
DOI :
10.1109/PCICON.2012.6549649
Filename :
6549649
Link To Document :