Pre-breakdown current in long point-plane transformer oil gaps with insulating barrier under AC voltage
Author :
Guerbas, F. ; Boubakeur, A. ; Beroual, A.
Author_Institution :
Lab. de Haute Tension, Ecole Nat. Polytech., Algiers, Algeria
fYear :
2011
fDate :
16-19 Oct. 2011
Firstpage :
744
Lastpage :
747
Abstract :
In this paper we present results of carried out investigations on the influence of insulating barriers on AC prebreakdown current of long point-plane transformer oil gaps up to 12cm. The insertion of an insulating barrier leads to an important prebreakdown current decrease. The barrier acts as a geometrical and electrostatic obstacle for the disruptive discharge. We present in the paper a comparison between the prebreakdown current in the system with barrier to that one without barrier. We have considered the parameters of the barrier such as its position between the electrodes, and its nature. We observe that the evolution of the pre-breakdown current versus the applied voltage has a capacitive behavior. The equivalent impedance of the oil gap is deduced from the experimental current-voltage characteristics.
Keywords :
electric breakdown; electrodes; electrostatics; power transformer insulation; transformer oil; AC pre-breakdown current; AC voltage; capacitive behavior; disruptive discharge; electrode; electrostatic obstacle; experimental current-voltage characteristic; geometrical obstacle; insulating barrier insertion; long point-plane transformer oil gap; oil gap impedance; Discharges; Electrodes; Impedance; Oil insulation; Power transformer insulation; long point-plane gaps; pre-breakdown current; transformer oil;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena (CEIDP), 2011 Annual Report Conference on
Conference_Location :
Cancun
ISSN :
0084-9162
Print_ISBN :
978-1-4577-0985-2
Type :
conf
DOI :
10.1109/CEIDP.2011.6232763