DocumentCode
2526824
Title
System-wide power quality monitoring at the consolidated Edison company of New York
Author
Sabin, D. Daniel ; Dimitriu, Cristiana ; Doherty, Frank ; Santiago, David
Author_Institution
Electrotek Concepts, Inc., Beverly, MA, USA
fYear
2012
fDate
17-20 June 2012
Firstpage
870
Lastpage
875
Abstract
The power quality monitoring system (PQMS) at Con Edison integrates measurements from power quality monitors, digital protective relays, digital fault recorders, SCADA historians, phase angle sensors, battery monitoring systems, and smart meters. The PQMS is used for power quality event and trend analysis via desktop and web server applications. It also provides single-event and multi-event fault analysis. The PQMS serves a major role in automatic distribution fault notification and fault location. It also provides transmission feeder fault notification. The PQMS correlates all PQ monitor events, digital relay events, and DFR events with the Con Edison SCADA historian. It provides automatic single-event and multievent analysis of capacitor switching transients. The PQMS provides incipient fault detection functionality, notification, and location estimation. It includes statistical process control modules for assessing voltage and reactive power regulation. The PQMS also provides MAIFI calculations for overhead distribution feeders.
Keywords
power supply quality; power system faults; power system measurement; reactive power control; statistical process control; voltage control; DFR events; Edison company; MAIFI calculations; New York; PQMS; SCADA historians; automatic distribution fault notification; battery monitoring systems; capacitor switching transients; desktop; digital fault recorders; digital protective relays; fault location; location estimation; multievent fault analysis; overhead distribution feeders; phase angle sensors; power quality monitoring system; reactive power regulation; single-event fault analysis; smart meters; statistical process control modules; system-wide power quality monitoring; voltage regulation; web server; Indexes; Monitoring; Power quality; Relays; Sensors; Substations; fault location; geographic information system; power distribution faults; power distribution reliability; power quality; power system restoration; power system transients; relational databases;
fLanguage
English
Publisher
ieee
Conference_Titel
Harmonics and Quality of Power (ICHQP), 2012 IEEE 15th International Conference on
Conference_Location
Hong Kong
ISSN
1540-6008
Print_ISBN
978-1-4673-1944-7
Type
conf
DOI
10.1109/ICHQP.2012.6381264
Filename
6381264
Link To Document