DocumentCode
2532166
Title
Calculation of flashover voltage of polluted insulators under DC and AC voltages
Author
Guan, Zhicheng ; Zhang, Rongting
Author_Institution
Dept. of Electr. Eng., Tsinghua Univ., Beijing
fYear
1988
fDate
12-16 Sep 1988
Firstpage
229
Abstract
The flashover processes of polluted insulators under both DC and AC voltages were observed with a high-speed camera. Physical and mathematical models to describe the DC and AC flashover are proposed. A formula expressing the resistance of the remainder pollution layer of a polluted insulator is derived. As a result the flashover criteria of a polluted insulator can be calculated directly, and it is unnecessary to convert a real insulator of complex shape into an equivalent rectangle. Computer programs used to calculate the flashover criteria of polluted insulators under DC and AC voltages have been developed. Some arc phenomena, such as the arc-bridging between the sheds or ribs of insulators, the drift of the arc from the insulator surface, and the number of arcs in series before flashover, were considered in the computer programs. Experiments to determine the flashover voltages of some insulators with complex shapes were performed
Keywords
arcs (electric); electrical engineering computing; flashover; insulators; AC voltages; DC voltage; arc phenomena; arc-bridging; computer programs; flashover voltage; high-speed camera; mathematical models; polluted insulators; remainder pollution layer; Cameras; Flashover; Insulation; Mathematical model; Pollution; Shape; Surface contamination; Surface resistance; Transmission lines; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and Applications of Dielectric Materials, 1988. Proceedings., Second International Conference on Properties and Applications of
Conference_Location
Beijing
Type
conf
DOI
10.1109/ICPADM.1988.38376