DocumentCode
2532835
Title
AC flashover performance of iced insulators
Author
Sun, Chao ; Jiang, Xinyang ; Gu, Li ; Zhang, Juyong
Author_Institution
Dept. of Electr. Eng., Chongqing Univ.
fYear
1988
fDate
12-16 Sep 1988
Firstpage
249
Abstract
Relations are given for the AC flashover voltage of iced insulators in terms of the amount of ice, the conductivity of water at 0°C, the ambient temperature, and the length of an iced insulator string. The reasons why the flashover voltage of iced insulators decreases are analyzed. It is pointed out that the amount of ice and the conductivity of water at 0°C can be used as parameters for characterizing the flashover voltage of iced insulators. In the test it was found that there was a slight difference between the shapes of naturally iced and artificially iced insulators. This may be the cause of the differences observed between flashover voltages of these two kinds of iced insulators
Keywords
flashover; insulation testing; insulators; AC flashover performance; ambient temperature; flashover voltage; iced insulators; test; water conductivity; Circuit testing; Conductivity; Flashover; Ice surface; Insulation; Insulator testing; Leakage current; Temperature; Voltage; Wind speed;