Electromagnetic Interference on Secondary Systems of Substation Caused by Short-circuit Fault
Author
Xuehai, Gong ; Jinliang, He
Author_Institution
North China Electr. Power Res. Inst., Beijing
fYear
2007
fDate
23-26 Oct. 2007
Firstpage
206
Lastpage
211
Abstract
This paper analyzed the influences of different factors on the electromagnetic interferences applied on the secondary systems due to the short-circuit faults in substation. The secondary cables with sheath grounded in two terminals can effectively suppress the potential difference between the core and sheath of secondary cable. The influence of different factors on the potential difference between the core and sheath of secondary cable and sheath current are systematically studied in power frequency short-circuit fault. Analysis results show, when the secondary cable sheath is grounded in two terminals, the maximum potential differences applied on the insulation layer of the secondary cable can reach about 40% of the ground potential rise.
Keywords
cable sheathing; electromagnetic interference; power cable insulation; power system faults; substations; cable sheathing; electromagnetic interference; ground potential rise; power frequency short-circuit fault; secondary cables; sheath current; substation secondary systems; Cable insulation; Circuit faults; Communication system control; Conductors; Control systems; Electromagnetic interference; Grounding; Power system faults; Substations; Voltage control; electromagnetic interference; secondary system; short-circuit fault; substation;
fLanguage
English
Publisher
ieee
Conference_Titel
Electromagnetic Compatibility, 2007. EMC 2007. International Symposium on
Conference_Location
Qingdao
Print_ISBN
978-1-4244-1371-3
Electronic_ISBN
978-1-4244-1372-0
Type
conf
DOI
10.1109/ELMAGC.2007.4413467
Filename
4413467
Link To Document