Measured impedance for inter phase faults on next line and second circuit of a double circuit line
Author
Shateri, H. ; Jamali, S.
Author_Institution
Dept. of Electr. Eng., Iran Univ. of Sci. & Technol. (IUST), Tehran
fYear
2008
fDate
20-22 Dec. 2008
Firstpage
331
Lastpage
336
Abstract
Distance relays are one of the mostly used protective devices in the transmission systems. These relays are used as the main, the first zone and a part of the second zone, and the backup, the rest of the second zone and the third zone, protective devices. Fault resistance is a source of error for distance relays in the form of the measured impedance deviation from its actual value. This paper compares the measured impedance a by distance relay on a double circuit line for the faults on the next line and the second circuit of the line, in the case of inter phase, phase to phase and three phase, faults. This is done by presenting the measured impedance at the relaying point and distance relay ideal tripping characteristic. The variation of the ideal tripping characteristic due to the changes in the power system parameters is investigated.
Keywords
power transmission faults; power transmission protection; relay protection; distance relays; double circuit line; fault resistance; interphase faults; phase to phase faults; protective devices; three phase faults; transmission systems; Circuit faults; Electrical resistance measurement; Impedance measurement; Phase measurement; Power system dynamics; Power system faults; Power system measurements; Power system protection; Power system relaying; Protective relaying;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical and Computer Engineering, 2008. ICECE 2008. International Conference on
Conference_Location
Dhaka
Print_ISBN
978-1-4244-2014-8
Electronic_ISBN
978-1-4244-2015-5
Type
conf
DOI
10.1109/ICECE.2008.4769227
Filename
4769227
Link To Document