Abstract :
The authors describe a method of measuring tgδ (loss tangent) and C (capacitance) of a single-phase apparatus with capacitive insulation by using an ordinary Schering bridge which takes the secondary voltage of a same-phase power transformer as the voltage of the standard arm and suppresses interference. Examples are given to illustrate how to analyze the results of measurement. The proposed method is safe and reliable, since testers need not come into contact with the high-voltage side of the apparatus, and a series of safety measures are taken. Because errors and interference are eliminated, the measuring data is stable and the accuracy high
Keywords :
capacitance measurement; dielectric loss measurement; high-voltage techniques; insulation testing; loss-angle measurement; measurement errors; power apparatus; HV apparatus; Schering bridge; capacitance measurement; capacitive insulation; error elimination; high-voltage; interference suppression; loss tangent measurement; safety measures; single-phase electrical apparatus; Bridge circuits; Capacitance measurement; Interference suppression; Loss measurement; Measurement standards; Power measurement; Power transformer insulation; Power transformers; Safety; Testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Properties and Applications of Dielectric Materials, 1988. Proceedings., Second International Conference on Properties and Applications of
Conference_Location :
Beijing
Type :
conf
DOI :
10.1109/ICPADM.1988.38496
Filename :
38496
Link To Document :
بازگشت