• DocumentCode
    2542075
  • Title

    Measured impedance by distance relay elements in a single phase to ground fault

  • Author

    Shateri, H. ; Jamali, S.

  • Author_Institution
    Dept. of Electr. Eng., Iran Univ. of Sci. & Technol., Tehran
  • fYear
    2008
  • fDate
    20-22 Dec. 2008
  • Firstpage
    682
  • Lastpage
    687
  • Abstract
    Distance relays are one of the mostly used protective devices in the transmission systems. These relays are used as the main and backup protective device. Fault resistance is a source of error for distance relays in the form of the measured impedance deviation from its actual value. This paper discusses the measured impedance by six elements of distance relay first zone in the case of a single phase to ground (AG) fault. This is done by presenting the measured impedance at the relaying point and the distance relay ideal tripping characteristic for each element. The variation of the ideal tripping characteristic due to the changes in the power system parameters is investigated.
  • Keywords
    power system parameter estimation; power system protection; relay protection; relays; distance relay elements; fault resistance; ideal tripping characteristic; measured impedance; measured impedance deviation; power system parameters; protective devices; single phase to ground fault; Circuit faults; Electrical resistance measurement; Impedance measurement; Phase measurement; Power measurement; Power system faults; Power system measurements; Power system protection; Power system relaying; Protective relaying;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical and Computer Engineering, 2008. ICECE 2008. International Conference on
  • Conference_Location
    Dhaka
  • Print_ISBN
    978-1-4244-2014-8
  • Electronic_ISBN
    978-1-4244-2015-5
  • Type

    conf

  • DOI
    10.1109/ICECE.2008.4769296
  • Filename
    4769296