DocumentCode :
2546853
Title :
An investigation on the effectiveness of Scott transformer on harmonic reduction
Author :
Mazin, Hooman Erfanian ; Xu, Wilsun
Author_Institution :
Dept. of Electr. & Comput. Eng., Alberta Univ., Edmonton, AB
fYear :
2008
fDate :
20-24 July 2008
Firstpage :
1
Lastpage :
4
Abstract :
Scott transformer is widely used in electric railway systems when there are two unbalanced single-phase loads. The transformer reduces unbalance current. This paper investigates that if Scott transformer can also reduce the harmonic current. Our study shows that when there are two harmonic-producing loads connected to each single-phase side of the transformer, the harmonics produced by loads will cancel out at the primary sides of the transformer and results in less harmonic current seen from the utility side. The amount of cancellation is affected by harmonic order and the size of loads.
Keywords :
harmonics suppression; power supply quality; power transformers; railway electrification; traction power supplies; Scott transformer; electric railway systems; harmonic current reduction; single-phase transformer; unbalance current reduction; unbalanced single-phase loads; Current measurement; Power measurement; Power quality; Power supplies; Power system harmonics; Power system measurements; Power system modeling; Power system simulation; Rail transportation; Harmonics; Scott transformer; traction loads;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Society General Meeting - Conversion and Delivery of Electrical Energy in the 21st Century, 2008 IEEE
Conference_Location :
Pittsburgh, PA
ISSN :
1932-5517
Print_ISBN :
978-1-4244-1905-0
Electronic_ISBN :
1932-5517
Type :
conf
DOI :
10.1109/PES.2008.4596926
Filename :
4596926
Link To Document :
بازگشت