DocumentCode :
2548333
Title :
Simulation study of conventional and hybrid HVDC rectifier based on CIGRÉ benchmark model using PLL-less synchronisation scheme
Author :
Das, Bhaba Priyo ; Watson, Neville ; Liu, Yonghe
Author_Institution :
Dept. of Electr. & Comput. Eng., Univ. of Canterbury, Christchurch, New Zealand
fYear :
2011
fDate :
6-7 June 2011
Firstpage :
312
Lastpage :
317
Abstract :
The objective of this paper is to compare and assess the performance of the conventional and hybrid high voltage direct current (HVDC) rectifiers based on the CIGRE benchmark model for both static and dynamic conditions with the phase lock loop (PLL) control replaced by PLL-less control. Traditional HVDC rectifier uses a 12-pulse thyristor bridge whereas the hybrid HVDC rectifier is based on one 6-pulse thyristor bridge and one 6-pulse diode bridge. Simulations are carried out in Matlab/Simulink. Some of the simulation results show that the hybrid option doesn´t look too attractive in spite of the cost savings it offers.
Keywords :
HVDC power transmission; phase locked loops; rectifiers; CIGRE benchmark model; PLL-less synchronisation scheme; high voltage direct current; hybrid HVDC rectifier; phase lock loop control; Bridge circuits; Firing; HVDC transmission; Harmonic analysis; Rectifiers; Synchronization; Voltage fluctuations;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering and Optimization Conference (PEOCO), 2011 5th International
Conference_Location :
Shah Alam, Selangor
Print_ISBN :
978-1-4577-0355-3
Type :
conf
DOI :
10.1109/PEOCO.2011.5970433
Filename :
5970433
Link To Document :
بازگشت