Title :
Measurement of overall power loss for different three phase 100kVA transformer core material
Author :
Ashbahani, N. ; Daut, Ismail ; Halim, N.H.
Author_Institution :
Sch. of Electr. Syst., Univ. Malaysia Perlis, Arau, Malaysia
Abstract :
This paper discussed result of an investigation towards the effect of using two different Cold Rolled Grain-Oriented (CRGO) Silicon Iron material to the 100kVA three phase distribution transformer. This experiment used M4 and M5 material with 5mm different overlap length, configured with yoke and limb arrangement. Power loss has been measured using no-load test with 15 layer of lamination. The power loss of the transformer model core of M4 material at the operation mode flux density, 1.5T is 0.976W/Kg. This shows that M4 material have lower overall power loss compare to M5 material where M5 material have 1.060W/Kg overall power loss during operation mode.
Keywords :
iron; power transformers; silicon; transformer cores; CRGO silicon iron; M4 material; M5 material; Si-Fe; apparent power 100 kVA; cold rolled grain-oriented; core material; flux density; limb arrangement; magnetic flux density 1.5 T; power loss measurement; three phase distribution transformer; yoke arrangement; Loss measurement; Phase transformers; Silicon; Steel; Transformer cores; Grain-Oriented Silicon Iron; M4 and M5 material; power loss; transformer core;
Conference_Titel :
Power Engineering and Optimization Conference (PEOCO), 2011 5th International
Conference_Location :
Shah Alam, Selangor
Print_ISBN :
978-1-4577-0355-3
DOI :
10.1109/PEOCO.2011.5970437