DocumentCode :
255701
Title :
Investigation of negative sequence injection capability in H-bridge multilevel STATCOM
Author :
Behrouzian, Ehsan ; Bongiorno, Massimo ; Zelaya De La Parra, Hector
Author_Institution :
Chalmers Univ. of Technol., Gothenburg, Sweden
fYear :
2014
fDate :
26-28 Aug. 2014
Firstpage :
1
Lastpage :
10
Abstract :
The aim of this paper is to investigate the ability of star- and delta-connected H-bridge multilevel STATCOMs to exchange negative-sequence current with the grid. Zero-sequence injection is utilized for capacitor voltage balancing. It is shown that a singularity for these configurations exists, leading to limitations in the utilization of the compensator for asymmetry compensation purposes.
Keywords :
power convertors; static VAr compensators; H-bridge multilevel STATCOM; capacitor voltage balancing; negative sequence injection capability; Automatic voltage control; Capacitors; Converters; Legged locomotion; Reactive power; Topology; Multilevel converters; Reactive power; Static Synchronous Compensator (STATCOM);
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics and Applications (EPE'14-ECCE Europe), 2014 16th European Conference on
Conference_Location :
Lappeenranta
Type :
conf
DOI :
10.1109/EPE.2014.6910883
Filename :
6910883
Link To Document :