Abstract
The aim of this paper is to investigate the ability of star- and delta-connected H-bridge multilevel STATCOMs to exchange negative-sequence current with the grid. Zero-sequence injection is utilized for capacitor voltage balancing. It is shown that a singularity for these configurations exists, leading to limitations in the utilization of the compensator for asymmetry compensation purposes.
Keywords
power convertors; static VAr compensators; H-bridge multilevel STATCOM; capacitor voltage balancing; negative sequence injection capability; Automatic voltage control; Capacitors; Converters; Legged locomotion; Reactive power; Topology; Multilevel converters; Reactive power; Static Synchronous Compensator (STATCOM);