• DocumentCode
    2557989
  • Title

    Basic studies on extrusion molded joints for high-voltage XLPE cables

  • Author

    Fukunaga, Sadao ; Yatuka, Ken ; Ban, Shun-ichiro ; Hirotu, Ken-ichi

  • Author_Institution
    Sumitomo Electr. Ind. Ltd., Osaka, Japan
  • fYear
    1990
  • fDate
    3-6 Jun 1990
  • Firstpage
    300
  • Lastpage
    304
  • Abstract
    The relation between jointing condition and interface microcavity generation was investigated for extrusion molded joints (EMJs) for XLPE (cross-linked polyethylene) cable. In addition, the relation between jointing condition and water generation in the cable´s reheated part was studied for the purpose of finding the optimum jointing condition that does not degrade electrical characteristics. Ways to eliminate microcavities on the interface and extra-long bow-tie trees in the middle layer of the reheated part have been investigated
  • Keywords
    cable jointing; high-voltage techniques; insulation testing; organic insulating materials; polymers; power cables; bow-tie trees elimination; cross-linked polyethylene; extra-long bow-tie trees; extrusion molded joints; high-voltage XLPE cables; interface microcavity generation; jointing condition; microcavities elimination; on-site extrusion; optimum jointing condition; water generation; Breakdown voltage; Cable insulation; Noise generators; Optical noise; Partial discharges; Polyethylene; Power transformer insulation; Semiconductivity; Semiconductor device noise; Trees - insulation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 1990., Conference Record of the 1990 IEEE International Symposium on
  • Conference_Location
    Toronto, Ont.
  • ISSN
    1089-084X
  • Type

    conf

  • DOI
    10.1109/ELINSL.1990.109760
  • Filename
    109760