Abstract :
Summary form only given. Methods used to establish and calibrate a 10-500/ square root 3 kV power frequency voltage ratio standard system are described. The standards are a series of capacitive dividers. which are calibrated at 6 kV with an inductive voltage divider but used at the higher operating voltages. Four potential transformers, used as 10-, 35-, 110/ square root 3-, and 220/ square root -kV working standards, were calibrated by the new system. Another potential transformer, which had been calibrated at the National Research Council of Canada (NRC) in September/October 1987, was also calibrated with the new system. The results indicate uncertainties of less than 10 parts per million and confirm the comparison with NRC.<>
Keywords :
calibration; high-voltage techniques; measurement standards; potential transformers; voltage dividers; voltage measurement; 10 kV; 35 kV; 6 kV; NRC; calibration; capacitive dividers; inductive voltage divider; potential transformers; power frequency voltage ratio national standard; working standards; Bridge circuits; Capacitance; Capacitors; Dielectric losses; Low voltage; Uncertainty; Voltage transformers;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Precision Electromagnetic Measurements, 1990. CPEM '90 Digest., Conference on
Conference_Location :
Ottawa, Ontario, Canada
Type :
conf
DOI :
10.1109/CPEM.1990.109972
Filename :
109972
Link To Document :
بازگشت