DocumentCode :
2562811
Title :
Post-arc currents of vacuum interrupters with axial magnetic field contacts under high current and voltage stress
Author :
Steinke, K. ; Lindmayer, M. ; Weltmann, K.-D.
Author_Institution :
Inst. fur Hochspannungstechnik und Elektrische Energieanlagen, Tech. Univ. Braunschweig, Germany
Volume :
2
fYear :
2000
fDate :
2000
Firstpage :
475
Abstract :
The post-arc current of vacuum interrupter units with bipolar axial magnetic field contacts has been investigated under conditions of high current (40 to 60 kA RMS) and high steepness of the transient recovery voltage (5 and 10 kV/μs). The arcing time and contact distance, respectively, has been changed by varying the moment of contact separation. By comparison with simulations, the measured clear decrease of the post-arc current and charge with decreasing arcing time can be attributed to lower residual ionization. The dependence of the post-arc current on du/dt is explained by the influence of secondary emission
Keywords :
circuit-breaking arcs; electrical contacts; magnetic fields; switchgear testing; vacuum arcs; vacuum interrupters; 40 to 60 kA; arcing time; axial magnetic field contacts; contact distance; contact separation; residual ionization; secondary emission; transient recovery voltage; vacuum interrupter post-arc currents; Anodes; Cathodes; Charge measurement; Current measurement; Electrons; Interrupters; Magnetic fields; Plasma density; Stress; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 2000. Proceedings. ISDEIV. XIXth International Symposium on
Conference_Location :
Xi´an
Print_ISBN :
0-7803-5791-4
Type :
conf
DOI :
10.1109/DEIV.2000.879030
Filename :
879030