DocumentCode
2563568
Title
Compensation of voltage drop using static VAr compensator at sectioning post in AC electric railway system
Author
Kawahara, Keiji ; Hase, Shin-ichi ; Mochinaga, Yoshifumi ; Hisamizu, Yasuji ; Inoue, Takashi
Author_Institution
Railway Tech. Res. Inst., Tokyo, Japan
Volume
2
fYear
1997
fDate
3-6 Aug 1997
Firstpage
955
Abstract
In this paper, the authors describe the application of SVC (static VAr compensator) to AC electric railway system, outlines SVC installed at Shin-syo sectioning post on San-yo Shinkansen and report on the result of verifiable site investigations. Single-phase SVC can reduce the voltage drop in the feeding circuit and improve the power factor at the substation by compensating the reactive power. In the case of compensating the voltage drop, it is more effective to locate the SVC at a sectioning post than at a substation. The site investigation has revealed that SVC can reliably suppress the voltage drop
Keywords
distribution networks; power factor; railways; reactive power; static VAr compensators; substations; AC electric railway system; San-yo Shinkansen; Shin-syo sectioning post; feeding circuit; power factor improvement; reactive power compensation; sectioning post; static VAr compensator; substation; voltage drop compensation; Capacitors; Circuits; Cities and towns; Impedance; Power system reliability; Rail transportation; Reactive power; Static VAr compensators; Substations; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Conversion Conference - Nagaoka 1997., Proceedings of the
Conference_Location
Nagaoka
Print_ISBN
0-7803-3823-5
Type
conf
DOI
10.1109/PCCON.1997.638383
Filename
638383
Link To Document