• DocumentCode
    2563568
  • Title

    Compensation of voltage drop using static VAr compensator at sectioning post in AC electric railway system

  • Author

    Kawahara, Keiji ; Hase, Shin-ichi ; Mochinaga, Yoshifumi ; Hisamizu, Yasuji ; Inoue, Takashi

  • Author_Institution
    Railway Tech. Res. Inst., Tokyo, Japan
  • Volume
    2
  • fYear
    1997
  • fDate
    3-6 Aug 1997
  • Firstpage
    955
  • Abstract
    In this paper, the authors describe the application of SVC (static VAr compensator) to AC electric railway system, outlines SVC installed at Shin-syo sectioning post on San-yo Shinkansen and report on the result of verifiable site investigations. Single-phase SVC can reduce the voltage drop in the feeding circuit and improve the power factor at the substation by compensating the reactive power. In the case of compensating the voltage drop, it is more effective to locate the SVC at a sectioning post than at a substation. The site investigation has revealed that SVC can reliably suppress the voltage drop
  • Keywords
    distribution networks; power factor; railways; reactive power; static VAr compensators; substations; AC electric railway system; San-yo Shinkansen; Shin-syo sectioning post; feeding circuit; power factor improvement; reactive power compensation; sectioning post; static VAr compensator; substation; voltage drop compensation; Capacitors; Circuits; Cities and towns; Impedance; Power system reliability; Rail transportation; Reactive power; Static VAr compensators; Substations; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Conversion Conference - Nagaoka 1997., Proceedings of the
  • Conference_Location
    Nagaoka
  • Print_ISBN
    0-7803-3823-5
  • Type

    conf

  • DOI
    10.1109/PCCON.1997.638383
  • Filename
    638383