• DocumentCode
    2564416
  • Title

    Verification of the seismic resistance of gas-insulated switchgear (GIS)

  • Author

    Buck, K.E. ; Kleine-Tebbe, A. ; Rees, V.

  • Author_Institution
    ABB Corp. Res., Heidelberg, Germany
  • fYear
    1991
  • fDate
    22-27 Sep 1991
  • Firstpage
    452
  • Lastpage
    458
  • Abstract
    A brief introduction into the background of seismic requirements is given. The test procedures are described, demonstrating the capability of gas insulated switchgear (GIS) to withstand seismic stresses up to highest ground accelerations of 0.75 g. The verification methods for checking the test object after test are described. As vibrational tests are very cost intensive and therefore can only be performed with a representative switchgear arrangement, calculation methods for demonstrating the seismic withstand behavior of practical switchgear arrangements are needed. A calculation model, adapted to the results of the representative seismic tests, is described. The tests and calculation results demonstrate the suitability of a 3 pole common enclosed GIS design for 145/170 kV for horizontal ground accelerations up to 0.75 g
  • Keywords
    gaseous insulation; switchgear testing; 145 kV; 170 kV; GIS; gas-insulated switchgear; horizontal ground accelerations; seismic resistance; test procedures; vibrational tests; Earthquakes; Gas insulation; Geographic Information Systems; Gravity; Performance evaluation; Stress; Substations; Switchgear; Testing; Vibrations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference, 1991., Proceedings of the 1991 IEEE Power Engineering Society
  • Conference_Location
    Dallas, TX
  • Print_ISBN
    0-7803-0219-2
  • Type

    conf

  • DOI
    10.1109/TDC.1991.169544
  • Filename
    169544