  • Abstract
    This paper describes a novel acoustic monitoring technique of insulation delaminations during a thermal cycling test (TC) on a stator bar. Acoustic signals emitted from insulation delaminations within the stator bar were continuously recorded during a TC test. An increase in measured acoustic signals indicates insulation delaminations within the stator bar under test. Dissipation factor tests, partial discharge tests, tap tests, and dissections were performed. Those diagnostic test results were compared with the acoustic test data to verify insulation delaminations. The acoustic monitoring system can indicate which cycle insulation delaminations occurred and when they occurred in a given thermal cycle during a TC test.
  • Keywords
    acoustic signal detection; delamination; insulation testing; machine windings; stators; thermal stresses; acoustic monitoring; acoustic signals; dissections; dissipation factor tests; insulation delaminations; partial discharge tests; stator bar; tap tests; thermal cycling tests; Acoustic emission; Acoustic measurements; Acoustic testing; Delamination; Insulation testing; Monitoring; Partial discharge measurement; Partial discharges; Performance evaluation; Stators;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation Conference, 2009. EIC 2009. IEEE
  • Conference_Location
    Montreal, QC
  • Print_ISBN
    978-1-4244-3915-7
  • Electronic_ISBN
    978-1-4244-3917-1
  • Type

    conf

  • DOI
    10.1109/EIC.2009.5166341
  • Filename
    5166341