DocumentCode
2564617
Title
New insights and complications in determining generator stator insulation absorption current exponents and constants from Polarization Index test data
Author
Milano, Bert ; Eastment, Eric ; Weeks, Benjamin
Author_Institution
Hydropower Tech. Services, U.S. Bur. of Reclamation, Denver, CO, USA
fYear
2009
fDate
May 31 2009-June 3 2009
Firstpage
254
Lastpage
258
Abstract
Significant errors may occur in calculating the generator insulation Polarization Index (PI), absorption current exponent (n), and the insulation constant (K), from standard PI test data. The paper addresses a previously undocumented PI response that occurs which is the cause of the subject errors. A simple approach is described to eliminate these errors especially when using the IEEE Standard 95-2002TM to correct for leakage current. IEEE Standard 43-2000TM is also useful regarding associated PI and insulation resistance calculations. In addition laboratory test data will be presented showing the relation between stator bar insulation temperature and the insulation constants K and n.
Keywords
IEEE standards; electric generators; machine insulation; permittivity; stators; IEEE standard 43-2000TM; IEEE standard 95-2002TM; absorption current exponent; generator insulation polarization index; generator stator insulation absorption current; insulation constant; Absorption; Aging; Dielectrics and electrical insulation; Equations; Insulation testing; Leakage current; Polarization; Stators; Temperature; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation Conference, 2009. EIC 2009. IEEE
Conference_Location
Montreal, QC
Print_ISBN
978-1-4244-3915-7
Electronic_ISBN
978-1-4244-3917-1
Type
conf
DOI
10.1109/EIC.2009.5166353
Filename
5166353
Link To Document