• DocumentCode
    2564617
  • Title

    New insights and complications in determining generator stator insulation absorption current exponents and constants from Polarization Index test data

  • Author

    Milano, Bert ; Eastment, Eric ; Weeks, Benjamin

  • Author_Institution
    Hydropower Tech. Services, U.S. Bur. of Reclamation, Denver, CO, USA
  • fYear
    2009
  • fDate
    May 31 2009-June 3 2009
  • Firstpage
    254
  • Lastpage
    258
  • Abstract
    Significant errors may occur in calculating the generator insulation Polarization Index (PI), absorption current exponent (n), and the insulation constant (K), from standard PI test data. The paper addresses a previously undocumented PI response that occurs which is the cause of the subject errors. A simple approach is described to eliminate these errors especially when using the IEEE Standard 95-2002TM to correct for leakage current. IEEE Standard 43-2000TM is also useful regarding associated PI and insulation resistance calculations. In addition laboratory test data will be presented showing the relation between stator bar insulation temperature and the insulation constants K and n.
  • Keywords
    IEEE standards; electric generators; machine insulation; permittivity; stators; IEEE standard 43-2000TM; IEEE standard 95-2002TM; absorption current exponent; generator insulation polarization index; generator stator insulation absorption current; insulation constant; Absorption; Aging; Dielectrics and electrical insulation; Equations; Insulation testing; Leakage current; Polarization; Stators; Temperature; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation Conference, 2009. EIC 2009. IEEE
  • Conference_Location
    Montreal, QC
  • Print_ISBN
    978-1-4244-3915-7
  • Electronic_ISBN
    978-1-4244-3917-1
  • Type

    conf

  • DOI
    10.1109/EIC.2009.5166353
  • Filename