An alternative evaluation of distribution transformers to achieve the lowest TOC
Author :
Baranowski, J.F. ; Hopkinson, P.J.
Author_Institution :
Cooper Industries Inc., Franksville, WI, USA
fYear :
1991
fDate :
22-27 Sep 1991
Firstpage :
571
Lastpage :
576
Abstract :
The 65°C rise rating of a distribution transformer is a thermal life rating of its insulation system, not a best efficiency condition. Total owning cost (TOC) is referenced at 85°C which is based on a 20°C ambient plus a 65°C rise. For better efficiency, a transformer should be operated at a lower temperature. Transformer design programs calculate a design for the lowest TOC at the 85°C reference temperature. These programs do not calculate a design for the lowest possible temperature rise or lowest TOC regardless of reference temperature. As a consequence, the lowest TOC is not realized. A new evaluation method is proposed that will provide the user with a distribution transformer design which has a lower operating temperature rise thus improving both the transformer´s efficiency and the customer´s TOC
Keywords :
economics; power transformers; 85 degC; distribution transformers; insulation system; thermal life rating; total owning cost; transformer efficiency; Core loss; Costs; Design optimization; Electrical equipment industry; Oil insulation; Power industry; Power systems; Power transformer insulation; Strontium; Temperature distribution;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference, 1991., Proceedings of the 1991 IEEE Power Engineering Society
Conference_Location :
Dallas, TX
Print_ISBN :
0-7803-0219-2
Type :
conf
DOI :
10.1109/TDC.1991.169561
Filename :
169561
Link To Document :
بازگشت