    Predicting and testing the effectiveness of voltage-correcting capacitors on two 12 kV distribution lines

  • Author

    Palmer, Richard H. ; Hackman, David E. ; Unger, Michael W. ; Oman, Henry

  • Author_Institution
    Vandenburg AFB, CA, USA
  • fYear
    1991
  • fDate
    22-27 Sep 1991
  • Firstpage
    653
  • Lastpage
    658
  • Abstract
    Techniques for calculating the quantity and locations of voltage-correcting capacitors on distribution lines have been described in many studies. Two different computer models to optimize the sizes and placement of capacitors on two 12 kV lines were used. One line is 16 km (10 miles) long with the biggest load, up to 2000 kVA, at its end. The other is 10.5 km (6.5 miles) long. After the capacitors were installed, loads and voltages were measured along each line while supplementing existing loads with load banks, one rated 2944 kVA and the other 500 kW. 200 HP fire pumps were started to collect transient performance. The measured currents and power factors were entered into the computer models to calculate voltages along the lines. Predicted voltages were, on the average, within 0.85% of measured values
  • Keywords
    distribution networks; load (electric); power capacitors; power engineering computing; transients; 12 kV; 200 hp; 2000 kVA; 2944 kVA; 500 kW; computer models; distribution lines; fire pumps; load banks; load measurement; power factors; testing; transient performance; voltage measurement; voltage-correcting capacitors; Atomic force microscopy; Capacitors; Current measurement; Military computing; Power measurement; Rails; Reactive power; Substations; Testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference, 1991., Proceedings of the 1991 IEEE Power Engineering Society
  • Conference_Location
    Dallas, TX
  • Print_ISBN
    0-7803-0219-2
  • Type

    conf

  • DOI
    10.1109/TDC.1991.169575
  • Filename
    169575