• DocumentCode
    2565365
  • Title

    Experience with field coil interconnection failures on large hydro generators Part I

  • Author

    Bomben, S.G. ; LeBlanc, J.-B.

  • Author_Institution
    Ontario Power Generation, Niagara-on-the-Lake, ON, Canada
  • fYear
    2009
  • fDate
    May 31 2009-June 3 2009
  • Firstpage
    463
  • Lastpage
    467
  • Abstract
    Over the last several years, Ontario Power Generation has experienced multiple field coil interconnection failures on several different machines in the same power-house of the same manufacturer. There have been other instances of this type of failure at other powerhouses within OPG, all with the same common manufacturer. The rotor of a large hydro generator is often a forgotten component of the machine and at times, little effort is put into assessing the condition of this critical component other than a simple reactance test and a low voltage insulation resistance test. The paper will discuss the numerous failures experienced, site investigation, and the solution implemented for one of the stations.
  • Keywords
    hydroelectric generators; machine testing; field coil interconnection failures; hydro generators; Assembly; Coils; Dielectrics and electrical insulation; Insulation testing; Lead; Manufacturing; Power generation; Rotors; Solids; Synchronous generators;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation Conference, 2009. EIC 2009. IEEE
  • Conference_Location
    Montreal, QC
  • Print_ISBN
    978-1-4244-3915-7
  • Electronic_ISBN
    978-1-4244-3917-1
  • Type

    conf

  • DOI
    10.1109/EIC.2009.5166391