• DocumentCode
    2565683
  • Title

    Condition monitoring of post insulators and surge arresters

  • Author

    Vitols, Arnold P. ; Stead, John

  • Author_Institution
    ABB Inc., Mount Pleasant, PA, USA
  • fYear
    2009
  • fDate
    May 31 2009-June 3 2009
  • Firstpage
    551
  • Lastpage
    554
  • Abstract
    The EXCOUNT II condition monitor was originally designed to measure impulse and resistive current in gapless metal oxide surge arresters. However in this study, it was determined that it can be applied to estimate the amount of insulator surface pollution and the associated need for washing the surface. AltaLink is establishing a schedule to monitor the contamination and download leakage current readings in order to set trigger levels for washing station post insulators. The benefit derived from this approach allows hot washing at lower levels in order to reduce the possibility of flashover at elevated pollution levels. This will help in decision making to maintain a more reliable power delivery system.
  • Keywords
    arresters; condition monitoring; flashover; insulator contamination; insulator testing; leakage currents; EXCOUNT II monitoring system; condition monitoring; flashover; gapless metal oxide surge arrester; insulator contamination; insulator surface pollution; leakage current; power delivery system reliability; station post insulator washing; Arresters; Condition monitoring; Current measurement; Flashover; Insulation; Leakage current; Pollution measurement; Power system reliability; Surface contamination; Surges;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation Conference, 2009. EIC 2009. IEEE
  • Conference_Location
    Montreal, QC
  • Print_ISBN
    978-1-4244-3915-7
  • Electronic_ISBN
    978-1-4244-3917-1
  • Type

    conf

  • DOI
    10.1109/EIC.2009.5166406
  • Filename
    5166406