DocumentCode
2565683
Title
Condition monitoring of post insulators and surge arresters
Author
Vitols, Arnold P. ; Stead, John
Author_Institution
ABB Inc., Mount Pleasant, PA, USA
fYear
2009
fDate
May 31 2009-June 3 2009
Firstpage
551
Lastpage
554
Abstract
The EXCOUNT II condition monitor was originally designed to measure impulse and resistive current in gapless metal oxide surge arresters. However in this study, it was determined that it can be applied to estimate the amount of insulator surface pollution and the associated need for washing the surface. AltaLink is establishing a schedule to monitor the contamination and download leakage current readings in order to set trigger levels for washing station post insulators. The benefit derived from this approach allows hot washing at lower levels in order to reduce the possibility of flashover at elevated pollution levels. This will help in decision making to maintain a more reliable power delivery system.
Keywords
arresters; condition monitoring; flashover; insulator contamination; insulator testing; leakage currents; EXCOUNT II monitoring system; condition monitoring; flashover; gapless metal oxide surge arrester; insulator contamination; insulator surface pollution; leakage current; power delivery system reliability; station post insulator washing; Arresters; Condition monitoring; Current measurement; Flashover; Insulation; Leakage current; Pollution measurement; Power system reliability; Surface contamination; Surges;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation Conference, 2009. EIC 2009. IEEE
Conference_Location
Montreal, QC
Print_ISBN
978-1-4244-3915-7
Electronic_ISBN
978-1-4244-3917-1
Type
conf
DOI
10.1109/EIC.2009.5166406
Filename
5166406
Link To Document