DocumentCode
2567431
Title
Critical switching impulse strength of long air gaps: modelling of air density effects
Author
Riz, F.A.M.
Author_Institution
Hydro-Quebec, Varennes, Que.
fYear
1991
fDate
22-27 Sep 1991
Firstpage
890
Lastpage
897
Abstract
A physical modelling approach is presented to investigate the effect of reduced air density on leader inception and sparkover of long air gaps under positive switching impulses with critical front time. The model accounts for the effect of air density on continuous leader inception voltage, leader length, and sparkover voltage. The results of the model provide critical positive switching impulse air density correction factors for rod-plane, rod-rod, conductor-plane, conductor-rod, and conductor-tower window gaps over a wide range of gap distances and relative air densities. The model findings were extensively checked against previous experimental results with quite satisfactory agreement
Keywords
electric breakdown of gases; sparks; switching; air density effects; conductor-plane gap; conductor-rod gaps; conductor-tower window gaps; continuous leader inception voltage; critical front time; critical switching impulse strength; gap distances; leader length; long air gaps; physical modelling; positive switching impulse air density correction factors; positive switching impulses; relative air densities; rod-plane gap; rod-rod gap; sparkover voltage; Air gaps; Electric breakdown; Flashover; Frequency; Humidity; Impulse testing; Insulation; Laboratories; Lightning; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference, 1991., Proceedings of the 1991 IEEE Power Engineering Society
Conference_Location
Dallas, TX
Print_ISBN
0-7803-0219-2
Type
conf
DOI
10.1109/TDC.1991.169609
Filename
169609
Link To Document