High-Resistance Grounded Power-System Equivalent Circuit Damage at the Line–Ground Fault Location—Part I
Author :
Paul, Deleglise
Author_Institution :
AECOM Technol. Corp., Oakland, CA, USA
Volume :
50
Issue :
6
fYear :
2014
fDate :
Nov.-Dec. 2014
Firstpage :
4179
Lastpage :
4187
Abstract :
This paper provides an electrical equivalent circuit of a high-resistance grounded (HRG) power supply transformer to discuss damage at a fault location so long as the fault remains a line-ground fault. Fault resistance and fault current that have an effect on damage are included in the equivalent circuit. Three-line diagrams showing fault current flows along with their vector diagrams are also included. Part II of this paper provides a similar equivalent circuit for an HRG grounded generator. This paper provides guidance to update the current edition of IEEE STD. 142 with respect to HRG systems.
Keywords :
earthing; equivalent circuits; fault currents; fault location; power system faults; power system protection; power transformers; HRG grounded generator; HRG power supply transformer; IEEE STD. 142; electrical equivalent circuit; fault current; fault resistance; high-resistance grounded power-system equivalent circuit damage; line-ground fault location; three-line diagrams; vector diagrams; Circuit faults; Fault currents; Grounding; Integrated circuits; Resistance; Resistors; Arcing fault; fault resistance; ground fault protection relay; high-resistance grounded (HRG) system; system charging current;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/TIA.2014.2346702
Filename :
6877703
Link To Document :
بازگشت