DocumentCode
2584577
Title
A fault tolerant converter topology for wind energy conversion system with doubly fed induction generator
Author
Gaillard, A. ; Karimi, Seemeen ; Poure, Philippe ; Saadate, Shahrokh ; Gholipour, Eskandar
Author_Institution
Nancy Univ., Nancy
fYear
2007
fDate
2-5 Sept. 2007
Firstpage
1
Lastpage
6
Abstract
This paper presents a novel fault tolerant converter topology for grid connected Wind Energy Conversion System (WECS) with Doubly Fed Induction Generator (DFIG). This topology allows fault detection and compensation of one of the semiconductors or drivers by using isolating and connecting devices. It is based on a unique redundant leg for both back to back converters. We present a new detection algorithm, robust to false fault detection due to semiconductor switching. Simulation results are presented for two open circuit cases on both back to back converters.
Keywords
asynchronous generators; fault diagnosis; fault tolerance; power convertors; wind power; doubly fed induction generator; fault detection; fault tolerant converter topology; semiconductor switching; wind energy conversion system; Detection algorithms; Driver circuits; Fault detection; Fault tolerant systems; Induction generators; Joining processes; Leg; Robustness; Topology; Wind energy; Doubly Fed Induction Generator; Fault Tolerant Converter Topology; Fault compensation; Fault detection; Wind Energy Conversion System;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics and Applications, 2007 European Conference on
Conference_Location
Aalborg
Print_ISBN
978-92-75815-10-8
Electronic_ISBN
978-92-75815-10-8
Type
conf
DOI
10.1109/EPE.2007.4417601
Filename
4417601
Link To Document