DocumentCode :
2588619
Title :
Error recovery for a boiler system with OTS PID controller
Author :
Anderson, Tom ; Feng, Mei ; Riddle, Steve ; Romanovsky, Alexander
Author_Institution :
Sch. of Comput. Sci., Newcastle upon Tyne Univ., UK
fYear :
2005
fDate :
2-4 Feb. 2005
Firstpage :
113
Lastpage :
120
Abstract :
We have previously presented initial results of a case study which illustrated an approach to engineering protective wrappers as a means of detecting errors or unwanted behaviour in systems employing an OTS (off-the-shelf) item. The case study used a Simulink model of a steam boiler system together with an OTS PID (proportional, integral and derivative) controller. The protective wrappers are developed for the model of the system in such a way that they allow detection and tolerance of typical errors caused by unavailability of signals, violations of range limitations, and oscillations. In this paper, we extend the case study to demonstrate how forward error recovery based on exception handling can be systematically incorporated at the level of the protective wrappers.
Keywords :
boilers; error detection; system recovery; three-term control; OTS PID controller; Simulink model; error detection; error recovery; off-the-shelf; proportional, integral and derivative controller; protective wrapper; steam boiler system; Boilers; Computer errors; Control systems; Error correction; Object oriented modeling; PD control; Pi control; Proportional control; Protection; Three-term control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Object-Oriented Real-Time Dependable Systems, 2005. WORDS 2005. 10th IEEE International Workshop on
ISSN :
1530-1443
Print_ISBN :
0-7695-2347-1
Type :
conf
DOI :
10.1109/WORDS.2005.34
Filename :
1544784
Link To Document :
بازگشت