DocumentCode :
2590562
Title :
A simple analysis on the performance of absorption heat pump system
Author :
Jeng, C.Y. ; Yo, Y.Y. ; Chuah, Y.K. ; Chu, P.H.
Author_Institution :
Ind. Technol. Res. Inst., Chutung, Taiwan
fYear :
1989
fDate :
6-11 Aug 1989
Firstpage :
2111
Abstract :
The performance of a single-stage LiBr/water absorption heat-pump (AHP) system in its cooling cycle is analyzed. Two important factors of the performance of an AHP are the effectiveness of the solution heat exchanger and the circulation ratio of the LiBr solution to water. In this analysis the cooling coefficient of performance (COP) of an AHP is expressed as an explicit function of the circulation ratio, the effectiveness of the solution heat exchanger, etc. The effects of the variation of different factors are analyzed. The optimal values of the effectiveness of the solution heat exchanger for an ideal cycle at various design conditions are presented, with the corresponding ideal COPs for the AHP cycle
Keywords :
cooling; heat exchangers; heat pumps; lithium compounds; LiBr; LiBr-H2O; absorption heat pump system; circulation ratio; coefficient of performance; cooling cycle; solution heat exchanger; Absorption; Cooling; Heat pumps; Heat recovery; Performance analysis; Power generation economics; Refrigerants; Temperature; Waste heat; Water heating;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Energy Conversion Engineering Conference, 1989. IECEC-89., Proceedings of the 24th Intersociety
Conference_Location :
Washington, DC
Type :
conf
DOI :
10.1109/IECEC.1989.74764
Filename :
74764