  • Abstract
    In order to reduce the size of transformers and simplify the lead design of them, the half-turn effect in three-phase autotransformers has been evaluated using the finite element analysis. In this paper, the transient analysis method using the external circuit which represents the three-phase load loss test condition is proposed to evaluate the change of load loss by the half-turn effect. From the result of the transient analysis, we found that the change of load loss by the half-turn effect in three-phase three-limb transformer did not occur and verified the above analysis result through the three-phase load loss measurement test. Therefore we think that the proposed analysis method can be used to evaluate the half-turn effect in three-phase autotransformers.
  • Keywords
    autotransformers; finite element analysis; loss measurement; finite element analysis; half-turn effect; three-phase autotransformers; three-phase load loss measurement test; transient analysis method; Circuit testing; Electrical equipment industry; Loss measurement; Magnetic analysis; Magnetic cores; Magnetic flux density; Numerical analysis; Power transformers; Transformer cores; Transient analysis;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electromagnetic Field Computation (CEFC), 2010 14th Biennial IEEE Conference on
  • Conference_Location
    Chicago, IL
  • Print_ISBN
    978-1-4244-7059-4
  • Type

    conf

  • DOI
    10.1109/CEFC.2010.5480548
  • Filename
    5480548