Title :
Ferroresonance in low-loss distribution transformers
Author_Institution :
GE Power syst. Energy Consulting, Schenectady, NY, USA
Abstract :
Field experience indicates that ferroresonance events occur more readily with low-loss distribution transformers, compared to distribution transformers with conventional loss levels. Extensive testing of a large number of transformers has shown a very strong and direct correlation between transformer core loss and the amount of capacitance needed to sustain a ferroresonant condition. A heuristic explanation is provided to show the important role of core loss in the ferroresonant circuit.
Keywords :
capacitance; ferroresonant circuits; losses; overvoltage; power transformers; transformer cores; capacitance; ferroresonance event; ferroresonant circuit; low-loss distribution transformer; temporary overvoltage; transformer core loss; Cables; Capacitance; Circuit testing; Costs; Ferroresonance; Frequency; Gaussian distribution; Guidelines; Surges; Transformer cores;