Title :
Comparison of DC breakdown voltage between multiple level test and successive discharge test methods
Author :
Phontusa, S. ; Chotigo, S.
Author_Institution :
Dept. of Electr. Eng., King Mongkut´´s Univ. of Technol., Bangkok
Volume :
2
fYear :
2008
fDate :
14-17 May 2008
Firstpage :
913
Lastpage :
916
Abstract :
This present work was a comparison of positive DC breakdown voltage obtained by ldquomultiple level testrdquo and ldquosuccessive discharge testrdquo methods following IEC 60-1 (1989) of a sphere-sphere gap in air. The experiment was done under actual different atmospheric condition, temperature and absolute humidity. The ratio of absolute humidity to the air density correction factor, h/gd, was in the range of 7-13 g/m3. The diameters of the sphere were 12.5 cm and 5 cm. The results found that the breakdown voltages obtained by multiple level and successive discharge methods were very close. The average difference of breakdown voltages from these 2 methods for 12.5 cm and 5 cm sphere was 1.33% and 1.05% respectively.
Keywords :
IEC standards; discharges (electric); DC breakdown voltage; IEC; absolute humidity; air density correction factor; atmospheric condition; multiple level test; sphere-sphere gap; successive discharge test methods; temperature humidity; Breakdown voltage; Circuit testing; Electrodes; Fault location; Humidity; IEC standards; Impulse testing; Lightning; Stress; Temperature;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology, 2008. ECTI-CON 2008. 5th International Conference on
Conference_Location :
Krabi
Print_ISBN :
978-1-4244-2101-5
Electronic_ISBN :
978-1-4244-2102-2
Type :
conf
DOI :
10.1109/ECTICON.2008.4600579
Filename :
4600579
Link To Document :
بازگشت