• DocumentCode
    2596309
  • Title

    The Effect of Temperature and Humidity on Radio Interference Generated from UHV DC Transmission Lines

  • Author

    Wang, Wei ; An, Bing ; Li, Chengrong ; Luo, Bing ; Li, Xiaolin ; Wang, Yixu ; Fan, Fei ; Yang, Bo

  • Author_Institution
    Beijing Key Lab. of High Voltage&EMC, North China Electr. Power Univ., Beijing
  • fYear
    2008
  • fDate
    26-29 Oct. 2008
  • Firstpage
    290
  • Lastpage
    292
  • Abstract
    To research the effect of temperature and humidity on radio interference generated from UHV DC transmission lines, a mini corona cage has been constructed and put in a manual environment room, which temperature and humidity can be controlled. At the same time, a radio interference performance measuring system by using loop method has been set up too. The radio interference generated from a copper line have been measured in a mini corona cage not only at different humidity from 30% to 99% at 20 but also at different temperature from 0 to 30. The relationship between radio interference level and temperature and humidity have been achieved.
  • Keywords
    HVDC power transmission; corona; humidity; power transmission lines; radiofrequency interference; UHV DC transmission lines; copper line; humidity effect; loop method; mini corona cage; radio interference; temperature effect; Copper; Corona; DC generators; Electromagnetic interference; Humidity control; Radio control; Temperature control; Time measurement; Transmission line measurements; Transmission lines;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 2008. CEIDP 2008. Annual Report Conference on
  • Conference_Location
    Quebec, QC
  • Print_ISBN
    978-1-4244-2548-8
  • Electronic_ISBN
    978-1-4244-2549-5
  • Type

    conf

  • DOI
    10.1109/CEIDP.2008.4772912