• DocumentCode
    2596425
  • Title

    The Characteristics of Winding Temperature for the Natural Ester Filled Transformer up to and Including 500 kVA

  • Author

    Lee, Byungsung ; Jeong, Jongman ; Park, Chulbae ; Song, Ilkeun

  • Author_Institution
    KEPRI KEPCO, Munjidong
  • fYear
    2008
  • fDate
    26-29 Oct. 2008
  • Firstpage
    115
  • Lastpage
    117
  • Abstract
    Because of environmental friendly and higher fire point, Natural ester fluids are widely used for transformer cooling materials. Natural ester has higher viscosity than that mineral oil. Top oil temperature and hottest temperature will be warmer when using natural ester fluid in transformers designed for conventional transformer oil. Although natural ester has less influence on deterioration of cellulose paper than mineral oil, an increased hottest temperature might have an effect on the aging of insulating paper in coil winding. When comparing natural ester with mineral oil at the same designed transformers up to 500 kVA. The deviation of hottest temperature between the two is increased with load. For preventing additional aging of insulation paper, design changes are required when substituting natural ester for conventional transformer oil.
  • Keywords
    ageing; coils; organic compounds; transformer oil; transformer windings; viscosity; aging; cellulose paper; coil winding; natural ester filled transformer; natural ester fluids; transformer cooling materials; transformer oil; viscosity; winding temperature; Aging; Coils; Cooling; Fires; Minerals; Oil insulation; Petroleum; Power transformer insulation; Temperature; Viscosity;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 2008. CEIDP 2008. Annual Report Conference on
  • Conference_Location
    Quebec, QC
  • Print_ISBN
    978-1-4244-2548-8
  • Electronic_ISBN
    978-1-4244-2549-5
  • Type

    conf

  • DOI
    10.1109/CEIDP.2008.4772918
  • Filename
    4772918