• DocumentCode
    2596495
  • Title

    Calculation of Current Rating for Medium and Low Voltage XLPE Cable in Clustered Layout

  • Author

    Youbin, Fan ; Shaoxin, Meng ; Fugui, Miao ; Li, Zhang ; Geng, Lan ; Yungang, Fan ; Yunjie, Zhou ; Yu, Li

  • Author_Institution
    Wuhan High Voltage Res. Inst., Wuhan
  • fYear
    2008
  • fDate
    26-29 Oct. 2008
  • Firstpage
    122
  • Lastpage
    124
  • Abstract
    For the clustered layout of power cable, the steady current rating of MV or LV XLPE cable in different laying status, in different temperatures of circumvents, and in different soil thermal resistances, was calculated according to the IEC 60287 standard. The effect of the temperature and the accuracy of soil resistance coefficient estimation with regards to the final results are also investigated. The result shows the coefficient of soil resistance plays the most important role in the current rating for cable in a clustered layout. Selecting an appropriate soil component is an important method to increase the current rating.
  • Keywords
    XLPE insulation; power cable insulation; XLPE cable; current rating; Cable shielding; Conductors; Ducts; Low voltage; Power cables; Soil; Surface resistance; Temperature; Thermal conductivity; Thermal resistance;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 2008. CEIDP 2008. Annual Report Conference on
  • Conference_Location
    Quebec, QC
  • Print_ISBN
    978-1-4244-2548-8
  • Electronic_ISBN
    978-1-4244-2549-5
  • Type

    conf

  • DOI
    10.1109/CEIDP.2008.4772921
  • Filename
    4772921