A two-stage PV grid-connected inverter with optimized anti-islanding protection method
Author
Xiang, Haitao ; Yan, Yangguang ; Jiang, Haijiang
Author_Institution
Coll. of Autom. Eng., Nanjing Univ. of Aeronaut. & Astronaut., Nanjing, China
fYear
2009
fDate
6-7 April 2009
Firstpage
1
Lastpage
4
Abstract
Anti-islanding protection of power disturbing method for a two-stage photovoltaic grid-connected inverter is designed in this paper. There is little coupling between the input and output power of the inverter as the dc-dc and dc-ac conversion is independent from each other. Step change of voltage across the dc-link filtering capacitor results in a change of stored energy of the capacitor and consequent a disturbance on the current injected into the grid. This algorithm is adopted for the islanding detection of the inverter. When the grid is gone, the disturbing current results in disturbance of the voltage across the ac terminals, and the islanding protection can be triggered. This method has merit of little non-detection zone for islanding detection.
Keywords
DC-AC power convertors; DC-DC power convertors; distributed power generation; invertors; power capacitors; dc-ac conversion; dc-dc conversion; dc-link filtering capacitor; inverter; islanding detection; islanding protection; optimized anti-islanding protection method; power disturbing method; two-stage photovoltaic grid-connected inverter; Capacitors; Change detection algorithms; Filtering; Inverters; Optimization methods; Photovoltaic systems; Power generation; Protection; Solar power generation; Voltage; Grid-Connected Inverter; Islanding Detection; Photovoltaic; Power disturbing; Two-Stage;
fLanguage
English
Publisher
ieee
Conference_Titel
Sustainable Power Generation and Supply, 2009. SUPERGEN '09. International Conference on
Conference_Location
Nanjing
Print_ISBN
978-1-4244-4934-7
Type
conf
DOI
10.1109/SUPERGEN.2009.5348245
Filename
5348245
Link To Document