DocumentCode
2606714
Title
The characteristics of electromagnetic current transformers with DC bias
Author
Li, Changyun ; Li, Qingmin ; Yao, Jinxia ; Liu, Min
Author_Institution
Sch. of Electr. Eng., Shandong Univ., Jinan, China
fYear
2009
fDate
6-7 April 2009
Firstpage
1
Lastpage
6
Abstract
Both geomagnetically induced currents (GIC) and high voltage direct current (HVDC) projects using the earth as its path can cause direct current flowing in the ground. Direct current flux will be produced and has detrimental effects on power systems. Few references can be found about the effects of dc bias on the current transformer that is very important to both metering and protective aims. In this paper, the characteristics of electromagnetic CTs are discussed. At first, the primary current is determined, and a decaying dc offset is found which will affect the CT´s dynamic performance. Then the CT´s steady state and transient state characteristics with dc bias are researched. It shows that the turns ratio, direct current and some other parameters have effects on the CT´s time-to-saturation which is important to protective engineers. EMTP simulation results confirm the validity of the results.
Keywords
HVDC power convertors; current transformers; DC bias; EMTP; electromagnetic current transformers; geomagnetically induced currents; high voltage direct current; Acceleration; Circuit faults; Current transformers; EMTP; Fault currents; HVDC transmission; Power system faults; Power system protection; Power system transients; Voltage; Current transformers; DC bias; EMTP; Percent error;
fLanguage
English
Publisher
ieee
Conference_Titel
Sustainable Power Generation and Supply, 2009. SUPERGEN '09. International Conference on
Conference_Location
Nanjing
Print_ISBN
978-1-4244-4934-7
Type
conf
DOI
10.1109/SUPERGEN.2009.5348387
Filename
5348387