    The Effect of GIS Apparatus Parameter on Very Fast transient Over-voltage

  • Author

    Tao, Meng ; Xin, Lin ; Jianyuan, Xu

  • Author_Institution
    Sch. of Electr. Eng., Shenyang Univ. of Technol., Shenyang, China
  • fYear
    2008
  • fDate
    9-12 Nov. 2008
  • Firstpage
    292
  • Lastpage
    295
  • Abstract
    Based on a hydro-energy storage station, the very fast transient over-voltage in GIS is calculated and simulated using the FORTRAN language and Matlab program. The node with the maximum of the VFTO is found. The suppression effect of cable and SF6 busbar is discussed, and the influence the shunted capacitor is analyzed in the paper. It is indicated that the VFTO peak-values may be restricted by increasing the length of the cable and the SF6 busbar properly, and frequency may be lowered. In addition, and the VFTO peak magnitude may be varied with the capacity of the shunted capacitor.
  • Keywords
    SF6 insulation; gas insulated substations; gas insulated switchgear; overvoltage protection; power apparatus; power cable insulation; power capacitors; transients; FORTRAN language; GIS apparatus; Matlab program; SF6 busbar; hydro-energy storage station; power cable; shunted capacitor; very fast transient over-voltage; Capacitance; Capacitors; Circuits; Frequency; Geographic Information Systems; Mathematical model; Power cables; Power system transients; Sulfur hexafluoride; Switches;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    High Voltage Engineering and Application, 2008. ICHVE 2008. International Conference on
  • Conference_Location
    Chongqing
  • Print_ISBN
    978-1-4244-3823-5
  • Electronic_ISBN
    978-1-4244-2810-6
  • Type

    conf

  • DOI
    10.1109/ICHVE.2008.4773931
  • Filename
    4773931