Effects of Series Reactor on Short-circuit Current and Transient Recovery Voltage
Author
Zhen-xin, GENG ; Xin, LIN ; Jian-yuan, XU ; Chi, TIAN
Author_Institution
Sch. of Electr. Eng., Shenyang Univ. of Technol., Shenyang
fYear
2008
fDate
9-12 Nov. 2008
Firstpage
524
Lastpage
526
Abstract
With the increasing of short-circuit current of the power grid, by use of series reactor to limit 500 kV short-circuit current is feasible, but the introduction of series reactor could change the transient recovery voltage and have effect on the circuit breakers interrupting performance. In this paper, 500 kV reactor is used to limit short-circuit current of Dongqing substation, the current changes of different reactor values under three-phase short-circuit fault are analyzed, the best-value work interval is obtained; at the same time, the problem of TRV is solved by the mean of introduction parallel capacitance, it can reduce the amplitude and rate of TRV. The results showed that: the way of using parallel capacitors to reduce amplitude and rate of TRV is feasible, if reduce the amplitude of the TRV substantially, larger capacitors are required.
Keywords
circuit breakers; power grids; reactors (electric); short-circuit currents; substations; Dongqing substation; circuit breakers; power grid; series reactor; short-circuit current; transient recovery voltage; voltage 500 kV; Circuit breakers; Circuit faults; Inductors; Power engineering and energy; Power grids; Power system reliability; Power system transients; Substations; Transient analysis; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
High Voltage Engineering and Application, 2008. ICHVE 2008. International Conference on
Conference_Location
Chongqing
Print_ISBN
978-1-4244-3823-5
Electronic_ISBN
978-1-4244-2810-6
Type
conf
DOI
10.1109/ICHVE.2008.4773988
Filename
4773988
Link To Document