DocumentCode
2609127
Title
Three-Dimensional Magneto-Thermal Fields Analysis of 1100kVGIS Disconnector
Author
Fan, Song ; Jianyuan, Xu ; Xin, Lin ; Li Wei
Author_Institution
Shenyang Univ. of Technol., Shenyang
fYear
2008
fDate
9-12 Nov. 2008
Firstpage
531
Lastpage
534
Abstract
The temperature rise of GIS disconnector is a fatal factor that affects the power grid service performance. In this paper, a three-dimensional finite element analysis model is established to analyze the magnetic-thermal field of 1100 kV GIS disconnector´s cabinet. The distribution of magnetic field intensity and the values of eddy currents are calculated in the magnetic field first. Then the eddy current loss is coupled into the fiuld-thermal field as a heat source to acquire the temperature rise value. Experimental values prove that this FEA model offers accurate results. So that the calculation method can be applied in the calculation of magneto-thermal fields to provide the accurate parameters for product design and shorted the design cycle.
Keywords
eddy current losses; finite element analysis; gas insulated substations; gas insulated switchgear; magnetic fields; power grids; thermal analysis; FEA model; GIS disconnector; eddy current loss; fatal factor; finite element analysis model; gas insulated substation; gas insulated switchgear; magnetic field intensity; power grid; three-dimensional magneto-thermal field analysis; Conducting materials; Conductors; Eddy currents; Finite element methods; Geographic Information Systems; Magnetic analysis; Magnetic fields; Power grids; Temperature; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
High Voltage Engineering and Application, 2008. ICHVE 2008. International Conference on
Conference_Location
Chongqing
Print_ISBN
978-1-4244-3823-5
Electronic_ISBN
978-1-4244-2810-6
Type
conf
DOI
10.1109/ICHVE.2008.4773990
Filename
4773990
Link To Document