    Performance Evaluation of 20 Years Old ZnO Surge Arresters Based on Laboratory Tests

  • Author

    Filho, Orsino Oliveira ; Barbosa, Flávio B. ; De Azevedo, Rogério M. ; Cruz, Waldenir A S ; Carvalho, Sylvia G.

  • Author_Institution
    CEPEL - Electr. Power Res. Center, Nova Iguacu
  • fYear
    2008
  • fDate
    9-12 Nov. 2008
  • Firstpage
    641
  • Lastpage
    644
  • Abstract
    Station ZnO surge arresters have been in service in 800 kV Brazilian substations for more than 20 years. There are also cases of some spare units of such arresters that have been stored for long time without being electrically stressed. As part of investigations about possible causes of a failure occurred in an important Brazilian 800 kV substation, old 800 kV ZnO arresters removed from service, as well as an unused spare, were tested in laboratory. Partial discharge, leakage current and residual voltage tests were carried out on each arrester section at CEPEL´s high voltage laboratory. Just one from a group of three 20 years old arresters removed from service presented acceptable performance. The unused spare arrester presented test results compatible with new ones.
  • Keywords
    arresters; partial discharges; wide band gap semiconductors; zinc compounds; ZnO; leakage current; partial discharge; residual voltage tests; surge arresters; Arresters; Current measurement; Laboratories; Leakage current; Partial discharges; Substations; Surges; Testing; Voltage; Zinc oxide;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    High Voltage Engineering and Application, 2008. ICHVE 2008. International Conference on
  • Conference_Location
    Chongqing
  • Print_ISBN
    978-1-4244-3823-5
  • Electronic_ISBN
    978-1-4244-2810-6
  • Type

    conf

  • DOI
    10.1109/ICHVE.2008.4774017
  • Filename
    4774017