DocumentCode :
2610564
Title :
Calculation of Very Fast Transient Overvoltages in GIS
Author :
Tiechen, Lu ; Bo, Zhang
Author_Institution :
High Voltage Dept., Wuhan Univ.
fYear :
2005
fDate :
2005
Firstpage :
1
Lastpage :
5
Abstract :
This paper refers to 500 kV gas insulated substation (GIS) of the Tian Huangping pumped storage power station in East China power system. With the current electro-magnetic transient program (EMTP) in world, we simulate and calculate the very fast transient overvoltages (VFTO) caused by operating of disconnect switch (DS), and the factors that influenced overvoltages. Otherwise we analyze the reason why the discharge counters of surge arrester acted frequently and the harm to transformer done by VFTO
Keywords :
EMTP; gas insulated substations; overvoltage; power system simulation; switching transients; 500 kV; East China power system; GIS; Tian Huangping pumped storage power station; disconnect switch; electro-magnetic transient program; gas insulated substation; surge arrester; transformer; very fast transient overvoltages; EMTP; Gas insulation; Geographic Information Systems; Power generation; Power system analysis computing; Power system simulation; Power system transients; Substations; Surges; Switches; EMTP; Gas Insulated Substation; Simulation; Very Fast Transient Overvoltages;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exhibition: Asia and Pacific, 2005 IEEE/PES
Conference_Location :
Dalian
Print_ISBN :
0-7803-9114-4
Type :
conf
DOI :
10.1109/TDC.2005.1546760
Filename :
1546760
Link To Document :