• DocumentCode
    2612397
  • Title

    Problems and countermeasures on safety of utility grid with a number of small-scale PV systems

  • Author

    Kobayashi, H. ; Takigawa, K. ; Hashimito, E. ; Kitamura, A. ; Matsuda, H.

  • Author_Institution
    Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
  • fYear
    1990
  • fDate
    21-25 May 1990
  • Firstpage
    850
  • Abstract
    Utility interconnection and control technologies for small-scale dispersed PV (photovoltaic) systems are being studied at the Rokko Island 200 kV PV test facility in Kobe, Japan. Some safety problems of the utility grid are being investigated. Some results of experiments conducted to date are reported. It was found that the operation of the protective relay installed in the utility substation is influenced by the PV systems´ power output on a short-circuit fault of the distribution line. In addition, it was confirmed that the automatic reclosing operation of the grid to separate the line fault section is interfered with by an islanding phenomenon. Some methods for preventing the run-on or islanding phenomenon on the distribution line with a number of PV systems were demonstrated, and results are reported
  • Keywords
    photovoltaic power systems; power system interconnection; safety; 200 kV; Japan; Kobe; PV test facility; Rokko Island; automatic reclosing operation; control technologies; line fault section; protective relay; safety; short-circuit fault; small-scale PV systems; utility grid; utility interconnection; Circuit faults; Circuit simulation; Circuit testing; Integrated circuit interconnections; Power system interconnection; Power system protection; Safety; Substations; System testing; Test facilities;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Photovoltaic Specialists Conference, 1990., Conference Record of the Twenty First IEEE
  • Conference_Location
    Kissimmee, FL
  • Type

    conf

  • DOI
    10.1109/PVSC.1990.111741
  • Filename
    111741